circuitcellar.com
Magazine Support   Digital Library   Products & Services   Suppliers Directory 
 
 





 

January 1998, Issue 90

Ground Zero:
A Real World Look at Lightning


by Steve Ciarcia & Jeff Bachiochi
Start It's All in the GroundingTransient Voldatge SupressionModem and Power-Line ProtectionUnplug the Computer! Automatic Thunderstorm Switch Black Box It Waiting for Summer Sources

BLACK BOX IT

The sample data distributed with the sensor demonstrated that the effective number of hits per minute the sensor picked up during a thunderstorm ranged from 30 to well over 300 (within a 100-mile radius, I suppose this is acceptable).

Personally, I’d be heading for the cellar if I saw an indication of a 300 hits-per-minute storm, but Jeff was fascinated at knowing the actual quantity. He included eight LEDs to provide a visual display of the hits per minute as a power of two.

Using this method, the first LED indicates two hits; the second, four hits; the third, eight hits; and so on. The last LED indicates 256 or greater hits per minute. The LEDs are off under clear-sky conditions.

To count hits from the sensor, Jeff used the T0CK1 input on a PIC16C54 microcontroller. Figure 3 shows the circuitry for this simple display. Besides the eight directly driven LEDs and T0CK1, there are three bits for configuration and a single-bit alarm output. The configuration bits choose how the alarm output functions.

Figure 3—The optical pulses are received from the lightning sensor and converted to a hits-per-minute LED indicator.

The output can be a 250-ms momentary pulse or continuously low during an alarm condition. The alarm trigger point is selected using the first two configuration bits. The four combinations select the hits-per-minute turn-on point of any of the upper four LEDs as its trigger level.

The software’s main loop contains a 3-s counting period, followed by a total of the last 20 periods (total over the last 1 min.). The total counts are transposed into a byte with the proper bit high to enable an LED indicating the appropriate range.

Because you want to know if the storm is moving toward or away from your location, it’s important to know about the past. Therefore, the PEAK count is displayed as a steady-state LED.

The PRESENT count is indicated by XORing the present count with the LEDs such that if PEAK and PRESENT are the same (as in a storm moving toward you), the LED flashes.

However, once PRESENT starts dropping, the peak-count LED remains steady and the present-count LED flashes. Now, you can tell immediately which direction the storm is heading. The PEAK value can be reset by pressing the reset button.

Although Jeff’s software only takes up about a quarter of the 16C54’s available code space, all of its registers are used. The majority are taken up by the 20 table entries doing the 3-s counting samples.

Only five other registers are used by the code for the rest of the functions. When no LEDs are on, the circuit requires only about 3 mA (add about 10 mA per LED).

Obviously, this whole circuit could operate from three alkaline batteries, but if it’s mounted where you plan to view the thunderstorm’s progress, trickle charging four NiCd batteries would be better. After all, when you need the information most to either pull the plug or tell you that conditions are all clear, you don’t want to depend on a tired set of batteries.

Figure 4 is the switch’s connect/disconnect section. This particular configuration accommodates AC power, coax, and phone lines.

Figure 4—The hits-per-minute converter also generates a "lightning alarm" output. This signal causes the circuit to physically disconnect the AC power, cable, and phone-line connections to the protected appliance.


The 16C54’s alarm output (set for steady-state output mode) drives an optoisolated triac switch controlling the AC power relay. The circuit’s normal condition is for the alarm output to be high and the relays energized. A small DC power supply, connected in parallel with the AC power relay coil, controls the coax and phone relays.

The switches’ output connections are made to the normally closed contacts. When the power is off or an alarm condition exists, the relays are deenergized. This connects the equipment side of things to ground, where it provides the greatest protection.

While the normal spacing of the relay contacts is less than ¼², should a high-voltage surge enter the line side of the switching unit, any place it arcs within the relay will be at ground. Certainly, if you incorporate MOV suppression in addition, such voltage levels shouldn’t even exit at the relays.

We didn’t include those MOVs and surge-suppression components on the schematic, but we indicated their proper placement. If you’re already using protection devices on these lines, you may not need to include them inside as well.